Rockwell-automation 1732E-OF4M12R ArmorBlock Dual-Port EtherNet/IP 4-P Manual de usuario Pagina 11

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 96
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 10
Rockwell Automation Publication 1732E-UM005A-EN-E - July 2012 3
Overview of the 1732E ArmorBlock Analog Input and Output Modules Chapter 1
Types of Modules
The Analog Input and Output modules are as follows.
Hardware/Software
Compatibility
The module and the applications described in this manual are compatible with
the following firmware versions and software releases.
Input and Output Types
The 1732E-IF4M12R module supports four input channels, while the
1732E-OF4M12R supports four output channels. Each of the four input/output
channels can be configured as either current or voltage input/output, with
current mode as default configuration.
You can select from a series of operational ranges for each channel. The range
designates the minimum and maximum signals that are detectable by the module.
To use an input or output as a current or voltage device, you must:
wire the input/output connector for the correct input type (see page 10
)
configure the input/output as current or voltage via RSLogix 5000
(see page 25
and page 35)
Alarms/Limits
The modules are capable of generating the following alarms:
process alarms (low, low-low, high, high-high) for 1732E-IF4M12R
clamp/limits alarm for 1732E-OF4M12R
Catalog Number Description Network
Connector
Power
Connector
1732E-IF4M12R 24V DC power, 4-Point Analog Input,
Dual-Port EtherNet/IP Module
Dual D-code
M12
Dual 4-pin
micro
1732E-OF4M12R 24V DC power, 4-Point Analog Output,
Dual-Port EtherNet/IP Module
Product Firmware Version / Software Release
1732E-IF4M12R and 1732E-OF4M12R Firmware rev. 1.1 or later
1756-EN2T, 1756-EN2TR, 1756-EN3TR 3.x version when using RSLogix 5000 v20 or later
RSLogix 5000 software 20 or later
RSLinx software 2.56 or later
Input/Output Ranges for 1732E-IF4M12R and 1732E-OF4M12R
Module Input/Output range
1732E-IF4M12R 0…20 mA
4…20 mA
0…10 V
-10…10 V
0…5 V
-5…5 V
1732E-OF4M12R
Vista de pagina 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 95 96