Rockwell-automation 1732E-OF4M12R ArmorBlock Dual-Port EtherNet/IP 4-P Manual de usuario Pagina 44

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 96
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 43
36 Rockwell Automation Publication 1732E-UM005A-EN-E - July 2012
Chapter 3 Configure Your Analog Input and Output Modules with RSLogix 5000 Software
Limits Configuration Tab
The Limits Configuration tab on the Module Properties dialog box lets you
program high and low limits, and disable and latch alarms per channel.
High Engineering High engineering value helps determine the engineering units the signal
values scale into. The high engineering term corresponds to the high signal
value. The scaling equation used is shown below.
Low Engineering Low engineering helps determine the engineering units the signal values
scale into. The low engineering term corresponds to the low signal value.
The scaling equation used is as follows:
Configuration tab
Field Description
Data =
(Signal-LowSignal)(HighEngineering-LowEngineering)
High Signal - Low Signal
+ Low Engineering
Data =
(Signal-LowSignal)(HighEngineering-LowEngineering)
High Signal - Low Signal
+ Low Engineering
Click Channel button to set limits
and alarm configuration for each
of the 4 channels.
Use the sliders to set limits. HI
sets High limits; and LO for Low.
Vista de pagina 43
1 2 ... 39 40 41 42 43 44 45 46 47 48 49 ... 95 96

Comentarios a estos manuales

Sin comentarios