62 Rockwell Automation Publication 1732E-UM005A-EN-E - July 2012
Chapter 5 Calibrate Your Modules
3. At the Output Range, choose the range from the pull-down menu to
calibrate the channels. Click Apply.
4. Click the Calibration Tab on the Module Properties dialog box.
5. Set the channels to be calibrated. In this example, all channels are enabled
for calibration.
6. Click Start Calibration to access the Calibration Wizard. This button is
active when:
the system is online, and
you selected at least one of the channels.
Note that you can press the F1 button on your keyboard or click Help from
the wizard and warning message that appear to get detailed information
about the procedures for calibration.
TIP
For the output module, calibration is done one channel at a time.