Rockwell Automation Publication 1732E-UM005A-EN-E - July 2012 37
Configure Your Analog Input and Output Modules with RSLogix 5000 Software Chapter 3
1. Choose from the options on the Limit Configuration tab.
2. After the channels are configured, do one of the following:
• Click Apply to store a change but stay on the dialog box to choose
another tab.
• Click OK to apply the change and close the dialog box.
• Click Cancel to close the dialog box without applying changes.
Limit Configuration tab
Field What to do Description
Channel Select apush button
to correspond to a
channel (0…3).
Refers to the channel being configured.
Click to configure.
Clamp Limits
High Clamp
Low Clamp
Type a high and low
clamp value that
limits the output
from the analog
module within this
range.
See Clamping/Limiting
on page 47 for more
information.
Disable All Alarms Click to check the
checkbox
Check the box to disable all alarms.
Important: When you disable all alarms, you
disable process, and channel diagnostic alarms (for
example, underrange and overrange). We
recommend that you disable only unused channels
so extraneous alarm bits are not set.
Latch Limit Alarms Click to check the
checkbox
Check the box to latch an alarm if the controller
data value exceeds the clamping limit.