ArmorPoint I/O 2-Port EtherNet/IP Adapter, Series A 17
Publication
1738-IN028B-EN-E - February 2010
Indicators 3 red/green status indicators on CPU:
- Adapter Status
- Network Status (Ports 1 and 2 combined)
- PointBus Status
1 green/yellow status indicator on CPU:
- Network Activity (Ports 1 and 2 combined)
2 green/yellow status indicators on base:
- Link 1 Activity/Status
- Link 2 Activity/Status
2 green power supply status indicators on DC-DC
converter:
- System Power (5V DC to PointBus Out)
- Adapter Power (24V DC from Field In)
Power consumption, maximum 10.4W @ 28.8V DC
Power dissipation, maximum 6.3W @ 28.8V DC
Thermal dissipation, maximum 21.5 BTU/hr @ 28.8V DC
Isolation voltage 50V (continuous), Basic Insulation Type
Field power bus voltage, nominal 24V DC
Field power bus supply voltage
range
10…28.8V DC range
Field power bus supply current,
maximum
10 A
Dimensions (H x W x D), approx. 112 x 123 x 67 mm (4.41 x 4.84 x 2.64 in.)
Wiring category
(2)
1 - on power ports
1 - on communications ports
General (Continued)