1 Publication 1756-UM521C-EN-P - July 2004
Appendix
A
Specifications
General Specifications
Module Location 1756 ControlLogix chassis
Backplane Current 1200mA @ 5.1V dc & 3mA @ 24V dc
Maximum Power Dissipation 6.19W
Thermal Dissipation 21.1 BTU/hr
Connecting Cable
Fiber Type
Fiber Termination Type
Assemblies
Maximum Length
Minimum Length
200/230 micron Hard Clad Silica (HCS),
Versalink V-System
Order from Rockwell Automation under catalog number
1403-CFxxx or use the Lucent Technologies
HCP-M0200T V01RK 200μm simplex cable
300m
1m
Operating Wavelength 650nm (red)
SynchLink Data Rate 5Mbps
Baud Rate 5Mbaud
Type of Communication Synchronous
Frame Period 50μs
Indicators Green and red indicators for operation, status and
diagnostics
Frame Parameters 3 Flags - 3 bytes
Control field - 1 byte
Data field - 24 bytes
CRC field - 2 bytes
Environmental Conditions
Operational Temperature IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 60°C (32 to 140°F)
Storage Temperature IEC 60068-2-1 (Test Ab, Un-packaged Non-operating
Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating
Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating
Thermal Shock):
-40 to 85°C (-40 to 185°F)
Relative Humidity IEC 60068-2-30 (Test Db, Un-packaged Non-operating
Damp Heat):
5 to 95% non-condensing