Split Range PID Logic
Block Block Type Parameter Element Value
PRESSURE Analog Input MODE_BLK TARGET Auto
XD_SCALE * EU_100
EU_0
UNITS_DECIMAL
DECIMAL
CHANNEL 1
L_TYPE Direct
PID PID MODE_BLK TARGET CAS
GAIN Loop
Dependent
RESET
RATE
PV_SCALE (these
values must
match in Analog
Input range)
EU_100
EU_0
UNITS_DECIMAL
DECIMAL
SPLIT Splitter MODE_BLK TARGET CAS
IN_ARRAY ** 0,48,50,100
OUT_ARRAY ** 100,0,0,100
VENT Analog Output MODE_BLK TARGET CAS
XD_SCALE * EU_100
EU_0
UNITS_DECIMAL
DECIMAL
CHANNEL 1
L_TYPE Direct
N2 Analog Input MODE_BLK TARGET CAS
XD_SCALE * EU_100
EU_0
UNITS_DECIMAL
DECIMAL
CHANNEL 1
L_TYPE Direct