Publication 1757-PM002A-EN-E - June 2006
Applications 4-31
12. Repeat steps 7-11 to connect the FFLD:0:I.In[1].InitPrimary tag to the
CVInitReq parameter.
This tag is the IN_1 pin from the RSFieldbus Logix Block and the FI
302 BKCAL_OUT.
This input stops the PIDE function block from generating an output in
the AO.
13. Click the Output Reference button .
The Output Reference is added to your sheet.
14. Drag and drop the Output Reference to the right of the PIDE block.