Publication 1757-PM002A-EN-E - June 2006
Fieldbus Status Codes for RSLogix E-7
Output Parameters
Fieldbus Status Logix Status - FFLD1:0:O.Out[0].xxxxxx
Quality Sub-status Limits WindupL WindupH Init Primary Initializing Initiate
Fault State
Fault State
Good
Cascade
Non-Specific Not Limited 0 0 0 0 0 0
Low Limited 1 0 0 0 0 0
High Limited 0 1 0 0 0 0
Constant 1 1 0 0 0 0
Initialization
Acknowledge
Not Limited 0 0 0 1 0 0
Low Limited 1 0 0 1 0 0
High Limited 0 1 0 1 0 0
Constant 1 1 0 1 0 0
Initialization
Request
Not Limited 0 0 1 0 0 0
Low Limited 1 0 1 0 0 0
High Limited 0 1 1 0 0 0
Constant 1 1 1 0 0 0
Initiate Fault
State
Not Limited 0 0 0 0 1 0
Low Limited 1 0 0 0 1 0
High Limited 0 1 0 0 1 0
Constant 1 1 0 0 1 0
Fieldbus Status Logix Status - FFLD1:0:0.AO[0].xxxxxx
Quality Sub-status Limits WindupL WindupH Init Primary Initializing Initiate
Fault State
Fault State
Bad Non-Specific Not Limited 0 0 0 0 0 1
Low Limited 1 0 0 0 0 1
High Limited 0 1 0 0 0 1
Constant 1 1 0 0 0 1