Publication 1757-PM002A-EN-E - June 2006
4-6 Applications
The Upstream Port must be 5 for the linking device to connect to the HSE
Host. Ports 1–4 are reserved for H1 ports.
3. Click OK.
The linking device is added to HSE.
Change the Root Bridge
1. Right-click the linking device and select Attributes.
2. Select Bridge for the BOF class and click OK.
3. Close the HSE window.
The Project window reflects your additions.
Create a New Fieldbus - H 1
1. In the Project window, right-click the linking device icon and select New
Fieldbus.
The New Fieldbus window opens.
2. Select H1 for the Type of Fieldbus.