2-18 Set Up A System
Figure 2.10 An Ideal Fieldbus Communications Signal
Good Network Scope Display
In order to analyze a fieldbus network signal, you must know what constitutes
a good signal versus a bad one.
Figure 2.11 represents a normal signal
consisting of two terminators.
Figure 2.11 Good Network Signal
(1)
(1)
FF Engineering Guide (11.4.3)
75-500 mv
75-500 mv
Max Noise
75 mv (pk-pk)