Publication 1761-UM005B-EN-P - October 2006
14 Quick Start
To configure a MicroLogix 1000 controller as a slave device to a
DeviceNet master, set the parameters as shown in the following table.
MicroLogix 1000 Controller Parameter Settings
Parameter Number Description Range Default Value For this Example,
ENTER
Series A Series B
4 1 Input Size Series A: 1…16
Series B: 1…32
1 word 2 words
Not Applicable 2 Input Split Point 1…32 1 word 2 words
5 3 Input Type Bit or Integer File Integer File Integer File
6 4 Input Data File 3…254 7 7
7 5 Input Word Offset 0…254 0 90
8 6 Output Size Series A: 1…16
Series B: 1…32
1 word 2 words
9 8 Output Type Bit or Integer File Integer File Integer File
10 9 Output Data File 3…254 7 7
11 10 Output Word Offset 0…254 1 95
14 11 DF1 Device 0…3:
0: Other
1: PLC
2: SLC/ Other
MicroLogix
3: MicroLogix 1000
3 = MicroLogix 1000 3 = MicroLogix 1000
312DNI Series A:
Data Enable
DNI Series B:
I/O Scan Enable
(Polling Enable)
Disabled (0) or Enabled
(1)
Disabled (0) Enabled (1)
12 13 DF1 Heartbeat Series A: 2…10
Series B: 1…10
22
13 14 Data Scan Delay
(Polling Delay)
20…3000 ms 50 ms 100 ms
2 15 Message Timeout 0…2500 ms 0 ms 0 ms
Not Applicable 16 DF1 Substitute Address 0…64 64 = Disabled 64 = Disabled
15 17 DF1 Autobaud Disabled (0) or Enabled
(1)
Enabled (1) Enabled (1)
16 18 DF1 Baud Rate 0…5:
0: 38,400
1: 19,200
2: 9600
3: 4800
4: 2400
5: 1200
Series A: 2 = 9600
Series B: 1 = 19,200
n/a
1 19 DeviceNet Autobaud Disabled (0) or Enabled
(1)
Enabled (1) Enabled (1)
17 Not
Applicable
DNI Mode Standby (0) or
Operational (1)
Operational (1) Operational (1)