DNI Configuration Parameters and Programming Notes 29
Input Size
This parameter identifies the size, in words, of the data array that is
read from the controller attached to the DNI’s RS-232 port.
The array may contain up to 16 (16-bit) words of data for DNI Series A
(32 words for DNI Series B) from a contiguous block within the
attached controller.
Messaging 2 15 Message Timeout 0…2500 ms 0 ms 46
Messaging Not
Applicable
16 DF1 Substitute
Address
0…64 64 = Disabled 47
DF1 15 17 DF1 Autobaud Disabled (0) or
Enabled (1)
Enabled (1) 47
DF1 16 18 DF1 Baud Rate 0…5:
0: 38,400
1: 19,200
2: 9600
3: 4800
4: 2400
5: 1200
Series A: 2 = 9600
Series B: 1 = 19,200
48
DeviceNet 1 19 DeviceNet Autobaud Disabled (0) or
Enabled (1)
Enabled (1) 48
Device 17 Not
Applicable
DNI Mode Standby (0) or
Operational (1)
Operational (1) 49
EDS Parameters for the DNI
Input Size Parameter Definition
Parameter
Type
Parameter Number Description Range Default
Value
Series
A
Series B
I/O 4 1 Input Size Series A: 1…16
Series B: 1…32
1
IMPORTANT
For DNI Series B, you must also configure the Input
Split Point.
See Input Split Point on page 30.