Publication 1761-UM005B-EN-P - October 2006
DNI Configuration Parameters and Programming Notes 33
Input Type
This parameter is used to identify the type of data to be read within
the controller. The DNI supports data exchange with either bit or
integer files.
Input Data File
This parameter is used to identify the data file to be read within the
controller. The following table shows the files within Allen-Bradley
controllers.
Parameter
Type
Parameter Number Description Range Default
Value
Series A Series B
I/O 5 3 Input Type Bit or Integer File Integer File
Parameter
Type
Parameter Number Description Range Default Value
Series A Series B
I/O 6 4 Input Data File 3…254 7
Controller Input Data Files Number Values
MicroLogix 1000 Bit 3
Integer 7
SLC/Other MicroLogix Bit 3, 10-255
Integer 7, 9-255
PLC Bit 3, 10-999
Integer 7, 9-999
TIP
The DNI can access only files 3…254.