50 Publication 1769-UM019A-EN-P - October 2008
Chapter 3 Module Data, Status, and Channel Configuration
Enable/Disable Channel (EC)
This configuration lets each channel be enabled individually. When a
channel is not enabled (EC = 0), the output channel is set to 0V or
0mA.
Program Mode (PM)
This configuration selection provides individual Program mode
selection for the output channels. When this selection is disabled
(PM = 0), the module holds the last state. This means that the output
remains at the last converted value prior to the condition that caused
the control system to enter Program mode.
If this selection is enabled (PM = 1), and the system enters the
Program mode, the module converts the user-specified value from the
channel’s Program Mode word to the appropriate analog output for
the range selected.
Bit Definitions for Output Range and Output Data Configuration Words
Define To choose Make these bit settings
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Output
Type/Range
Select
-10…10V DC
0000
0…5V DC
0001
0…10V DC
0010
4…20 mA
0011
1…5V DC
0100
0…20 mA
0101
Output Data
Format Select
Raw/Proportional
Counts
000
Engineering Units 001
Scaled for PID 010
Percent Range 011
IMPORTANT
Hold last state is the default condition for the module during a
control system Run-to-Program mode change.
TIP
N
Not all controllers support alternate output states and this
function. Refer to your controller’s user manual for details.