64 Publication 1769-UM019A-EN-P - October 2008
Chapter 4 Module Diagnostics and Troubleshooting
Invalid Input Range Selected
These error codes occur when the 4-bit input range code for the
indicated channel is not one of the assigned input range codes for the
module.
See Bit Definitions for Input Range and Input Data Configuration
Words on page 42 for details on the assigned input range codes for
each module.
X40D 010 0 0000 1101 Invalid alarm data (channel 0)
X40E 010 0 0000 1110 Invalid alarm data (channel 1)
X40F 010 0 0000 1111 Invalid alarm data (channel 2)
X410 010 0 0001 0000 Invalid alarm data (channel 3)
X411 010 0 0001 0001 Invalid input filter selected (channel 0)
X412 010 0 0001 0010 Invalid input filter selected (channel 1)
X413 010 0 0001 0011 Invalid input filter selected (channel 2)
X414 010 0 0001 0100 Invalid input filter selected (channel 3)
X415 010 0 0001 0101 Invalid output range selected (channel 0)
X416 010 0 0001 0110 Invalid output range selected (channel 1)
X417 010 0 0001 0111 Invalid output format selected (channel 0)
X418 010 0 0001 1000 Invalid output format selected (channel 1)
X419 010 0 0001 1001
Invalid output fault value selected (channel 0)
(2)
X41A 010 0 0001 1010
Invalid output fault value selected (channel 1)
(2)
X41B 010 0 0001 1011
Invalid output program/idle value selected (channel 0)
(2)
X41C 010 0 0001 1100
Invalid output program/idle value selected (channel 1)
(2)
X41D 010 0 0001 1101 Invalid output clamp value selected (channel 0)
X41E 010 0 0001 1110 Invalid output clamp value selected (channel 1)
X41F 010 0 0001 1111
Invalid ramp rate selected (channel 0)
(2)
X420 010 0 0010 0000
Invalid ramp rate selected (channel 1)
(2)
X421 010 0 0010 0001 Invalid real time sample value
(1) X represents the Don’t Care digit. Module configuration error codes are typically presented in their Hex Equivalent by the programming software.
(2) Some controllers do not support alternate output states. Refer to your controller user manual to determine whether alternate output states and these associated functions
are supported.
Extended Error Codes for Configuration Errors
Hex Equivalent
(1)
Module
Error Code
Extended Error
Information Code
Error Description
Binary Binary