Publication 1769-UM019A-EN-P - October 2008 57
Module Data, Status, and Channel Configuration Chapter 3
Valid Output Data Word Formats/Ranges
This table shows the valid formats and minimum/maximum data
ranges provided by the module.
Valid Output Data
Normal
Operating
Output Range
Full Range
(1)
Raw/
Proportional
Data
Engineering
Units
(2)
Scaled-for-PID
Percent Range
(3)
Full Range
Full Range Normal
Operating
Range
Full Range
Normal
Operating
Range
Full Range
-10…10V DC -10.5…10.5V
-32,764…
32,764
-10,500…10,500
0…16,380
-408…16,792 -10,000…
10,000
-10,500…10,500
0…5V DC -0.5…5.25V -500…5,248 -1638…17,200
0…10,000
-1000…10,500
0…10V DC -0.5…10.5V -500…10,500 -820…17,200 -500…10,624
1…5V DC 0.5…5.25V 500…5,248 -2048…17,404 -1250…10,624
0…20 mA 0…21 mA 0…21,000 0…17,200 0…10,500
4…20 mA 3.2…21 mA 3,200… 21,000 -820…17,404 -500…10,624
(1) Includes amounts over and under normal operating range.
(2) 1 count = 0.001V or 0.001 mA.
(3) 1 count = 0.01%.