Publication 1769-UM009E-EN-P - August 2009 57
Automatically Configure a DeviceNet Network Chapter 4
Access Device Data
When you add the scanner to the I/O configuration of the controller,
RSLogix 5000 software automatically creates a set of tags for the input, output,
and status data of the network:
The tags for your DeviceNet data follow this format:
input data from the scanner
status data from the scanner
output data for the scanner
location :type .Data IO_offset .bit
= Optional
Where Is
location location of the scanner in the system
If you have the 1769-SDN scanner in a Then location is
local chassis Local:slot_number_of_scanner
remote chassis adapter:slot_number_of_scanner
where:
adapter is the name of the EtherNet/IP or ControlNet module in
the remote chassis.
type type of data:
Where Is
input from a device I
output to a device O
IO_offset_address address of the device on the DeviceNet network (based on 4 bytes per node)
bit specific bit within the data of the device