Manually Configure the DeviceNet Network Chapter 5
3. Click the Configuration Recovery checkbox.
4. Click the Auto-Address Recovery checkbox if desired.
The Enable Auto-Address Recovery checkbox needs to be checked in
order for AAR to work.
5. Repeat steps 1...4 for each desired module.
Notice that Both indicates Configuration Recovery and Auto-Address
Recovery are enabled while Config indicates that only Configuration
Recovery is enabled.
6. When finished, click Download to Scanner.
7. Click Apply or OK.
Notice the ADR space (in
bytes) is displayed for the
module you are updating.