Rockwell-automation 1794-APBDPV1 FLEX I/O PROFIBUS Adapter User Manual Manual de usuario Pagina 141

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 153
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 140
Publication 1794-UM064B-EN-P - May 2014
128 Additional HART Protocol Information
Common Practice Commands
Command Data in Command Data in Reply
# Function Byte Data Type
(5)
Byte Data Type
(5)
33 Read transmitter
variables
—None
(2)
0 Transmitter variable code
for slot 0
1 Units code for slot 0
2…5 Variable for slot 0 (F)
6 Transmitter variable code
for slot 1
7 Units code for slot 1
8…11 Variable for slot 1 (F)
12 Transmitter variable code
for slot 2
(6)
13 Units code for slot 2
14…17 Variable for slot 2 (F)
18 Transmitter variable code
for slot 3
19 Units code for slot 3
20…23 Variable for slot 3 (F)
34 Write damping value 0…3 Damping value (seconds) (F) As in command (F)
35 Write range values 0 Range units code As in command (F)
1…4 Upper range value (F)
5…8 Lower range value (F)
36 Set upper range value
(push SPAN button)
—None —None
37 Set lower range value
(push ZERO button)
—None —None
38 Reset configuration
changed flag
—None —None
39 EEPROM control 0
(1)
EEPROM control code As in command
40 Enter/edit fixed current
mode
0…3 Current (mA)
(3)
(F) As in command
41 Perform device
self-test
—None —None
42 Perform master reset None None
43 Set (trim) PV zero None None
44 Write PV units 0 PV units code As in command
45 Trim DAC zero 0…3 Measured current (mA) As in command
46 Trim DAC gain 0…3 Measured current (mA) (F) As in command
47 Write transfer function 0 Transfer function code As in command