Publication 1794-UM064B-EN-P - May 2014
Additional HART Protocol Information 129
48 Read additional device
status
None 0…5 Device-specific status (B)
6…7 Operational modes
8…10 Analog outputs
saturated
(7)
(B)
11…13 Analog outputs fixed.
(8)
14…24 Device-specific status
49 Write PV sensor serial
number
0…2 Sensor serial number
number
As in command
50 Read dynamic variable
assignments
None 0 PV transmitter variable
code
1 SV transmitter variable
code
2 TV transmitter variable
code
3 FV transmitter variable
code
51 Write dynamic variable
assignments
0 PV transmitter variable
code
As in command
1 SV transmitter variable
code
2 TV transmitter variable
code
3 FV transmitter variable
code
52 Set transmitter
variable zero
0 Transmitter variable code As in command
53 Write transmitter
variable units
0 Transmitter variable code As in command
1 Transmitter variable
units code
54 Read transmitter
variable information
Transmitter variable code 0 Transmitter variable code
1…3 Transmitter variable
sensor serial number
4 Transmitter variable limit
units code
5…8 Transmitter variable upper
limit
(F)
9…12 Transmitter variable lower
limit
13…16 Transmitter variable
damping value (seconds)
17…20 Transmitter variable
minimum span
55 Write transmitter
variable damping value
0 Transmitter variable code As in command
1…4 Transmitter variable
damping value (seconds)
Common Practice Commands
Command Data in Command Data in Reply
# Function Byte Data Type
(5)
Byte Data Type
(5)