Publication 1794-UM064B-EN-P - May 2014
34 Communicate With Your Module
1794-IT8 Word/Bit Description
Word Dec. Bits
(Octal Bits)
Description
Write Word 0 00…01 Module Data Type
Bit 01 00 Definition
0 0 °C (default)
01°F
1 0 Bipolar counts scaled between -32768…32767
1 1 Unipolar counts scaled between 0…65535
02 Fixed Filter Enable – When this bit is set (1), a software digital filter is enabled. This filter settles to 100%
of a Full Scale step input in 60 scans.
03…05 Notch Frequency
Bit 05 04 03
0 0 0 10 Hz (default)
001 25 Hz
010 50 Hz
011 60 Hz
100 100 Hz
101 250 Hz
110 500 Hz
1 1 1 1000 Hz
06 Gain Offset Calibration – This bit is set during gain calibration/ reset during offset calibration.
07 Calibration Clock – This bit must be set to 1 to prepare for a calibration cycle; then reset to 0 to
initiate calibration.
08…15 (10…17) Calibration Mask – The channel, or channels, to be calibrated will have the correct mask bit set. Bit 0
corresponds to channel 0, bit 1 to channel 1, and so on.
Write Word 1 00…03 Channel 0 Thermocouple Type
Bit 03 02 01 00 Thermocouple Type – Range
0 0 0 0 Millivolts (default)
0 0 0 1 B 300...1800 °C (572...3272 °F)
0 0 1 0 E -270...1000 °C (-454...1835 °F)
0 0 1 1 J -210...1200 °C (-346...2192 °F)
0 1 0 0 K -71...1372 °C (-95...2502 °F)
0 1 0 1 R -50...1768 °C (-58...3214 °F)
0 1 1 0 S -50...1768 °C (-58...3214 °F)
0 1 1 1 T -73...400 °C (-99...752 °F)
1 0 0 0 C 0...2315 °C (32...4199 °F)
1 0 0 1 N -270...1300 °C (-450...2372 °F)