Rockwell-automation 198x Modular DeviceNet Starter Auxiliary I/O Manual de usuario Pagina 105

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 164
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 104
Specifications 5-39
Publication 198-UM001B-EN-P September 2001
Figure 5.28 Replacing Cat. No. 198-IA2XOW1 Series A module with Series B
ATTENTION
!
Make sure all power has been removed from the modules and all other
components inside the enclosure.
A2
A1
13
14
AC Starter Module
13
M
MS
M
L
N
23
24
MS
IN1
IN2
Out A
N
N
L
14
120V ac
1
2
3
4
6 7
-
Designates Terminal connections
on the 190 Compact starter
M – contactor
MS – manual starter
Step 1- Remove Plugs
Step 2- Remove Module
In 2
Out A
N
N
L
In 1
120V ac
Lout
A2
A1
13
14
13
M
MS
M
N
23
24
MS
14
1
2
3
5
6 7
Step 5- Remove
Jumper between
point 4 and 5
L
Step 3- Insert new Series B module
Step 4- Remove wires one at a time then place in to
the series B connector “L out” will be left blank
at this
time
Step 6- Add wire
between point 4 and
“L out”
Step 7- Insert all three plugs into
module
5
4