5-48 Specifications
Publication 198-UM001B-EN-P September 2001
198-IB2XOW1 Series A and B (DC Input Relay Output Module)
Figure 5.34 Cat. No. 198-IB2XOW1 Series A and B DC Input Relay Output Module
The DC input relay output module 198-IB2XOW1 is designed to control an AC starter with
coil voltage up to 250V AC. It consists of one relay output and two isolated DC inputs. The
two isolated DC inputs allow for status monitoring even when an E-stop has been executed.
The additional terminal is a +24V DC output. The output is not general purpose and is
designed for contact closure between the +24V DC output and the 198-IB2XOW1 module’s
inputs. The +24V DC output is isolated from the DeviceNet power via a DC-to-DC
converter. This module comes with a DIN Rail-Mount base but can be mounted next to any
gland plate-mounted device.
Series A to Series B Changes
V out terminal added
Inputs changed from sourcing to sinking