PLC-5 Data Pass–ThroughD–10
Publication 2706-6.2
1784-KTK1 Interface Module Set Up Parameters
Use the following when setting up the Pass-Through function.
DH + Connection Type
Select: Direct if your programming computer and your PLC-5 are
the only devices on the DH+ link or if there are multiple
devices on the link and your programming computer is the
first or last (physical) device on the link.
Select: Multi-Drop if there are multiple devices on the link and your
programming computer is not the first or last (physical)
device on the link.
KTK1 Address
The bit address that you assign to the 1784-KTK1 Module using the
DIP switch on the module.
KTK1 Interrupt
The interrupt that you assign to the 1784-KTK1 Module using the
jumper on the module. The factory setting for this interrupt is IRQ5.
1770-KF2 Interface Module Set Up Parameters
Use the following when setting up the Pass-Through function.
Configure Port
The computer port to which the KF2 Module is attached.
Select: COM1 or COM2
Baud Rate 300, 600, 1200, 2400, 4800, 9600
Parity None, Even, Odd
Duplex Half, Full
Error Checking CRC, BCC
These parameters must match the settings for the KF2 Module.