Chapter 15
DTAM Plus Background Monitor
15-6
Integer or BCD Selections
The register information for an Integer or BCD background register is shown
below.
Parameter Description
Register Number The PLC or SLC register number you want to monitor.
Low Alarm Limit The lowest value that is acceptable before an alarm state is
indicated.
High Alarm Limit The highest value that is acceptable before an alarm state is
indicated.
Low Return to Normal The predetermined value that the register data must exceed before
a new alarm state may be triggered. Defaults to the value of the low
alarm limit.
High Return to Normal The predetermined value that the register data must fall below
before a new alarm state may be triggered. Defaults to the value of
the high alarm limit.
Screen Number The number of the screen to display when the status of the
monitored register indicates an alarm state.