Chapter 3
Designing DTAM Plus and
DTAM Micro Applications
33
Both the DTAM Micro and DTAM Plus can read and write PLC and SLC
controller files. Refer to the following when designing applications.
PLC-5 File Types
File Type Supported By;
Integer
File Type
DTAM Plus
DTAM Micro
Read / Write Identifier File Number Element
Integer
Sub-Element
Bit Number
Output Yes Yes Read O 0
0-277
NA
0-17
Input Yes Yes
Read
I 1
0-277
NA
0-17
Status Yes Yes Read / Write S 2 0-127 NA 0-15
Bit (Binary) Yes Yes Read / Write B 3-999 0-999 NA 0-15999
Timer Yes Yes Read / Write T 3-999 0-999 PRE, ACC EN, TT, DN
Counter Yes Yes Read / Write C 3-999 0-99 PRE, ACC
CU, CD, DN.
OV, UN
Control Yes Yes Read / Write R 3-999 0-999 LEN, POS
EN, EU,
DN, EM, ER,
UL, IN, FD
Integer Yes Yes Read / Write N 3-999 0-999 NA 0-15
Floating Point Yes Yes (Limited) Read / Write F 3-999 0-999 NA NA
ASCII Yes Yes Read A 3-999 0-999 NA 0-15
BCD Yes Yes Read / Write D 3-999 0-999 NA 0-15
Block
Transfer
Yes No Read / Write BT 3-999 0-999 NA NA
Message Yes Yes Read MG 3-999 0-584
ERR, RLEN,
DLEN,
DATA 90-51)
NR, TO,
EN, ST, DN,
ER, CO, EW,
SD, SE
PID Yes No Read / Write PD 3-999 NA NA NA
SFC Yes No Read / Write SC 3-999 NA NA NA
ASCII String Yes Yes Read ST 3-999 0-799 LEN, CHAR 0-15
Octal format, all other values are decimal. Remote I/O allows the DTAM to write its own output words.
SLC File Types
File Type Supported By;
Integer
File Type
DTAM Plus
DTAM Micro
Read / Write Identifier File Number Element
Integer
Sub-Element
Bit Number
Output Yes Yes Read O 0 0-255 NA 0-15
Input Yes Yes Read I 1 0-255 NA 0-15
Status Yes Yes Read / Write S 2 0-82 NA 0-15
Bit (Binary) Yes Yes Read / Write B 3, 9-255 0-255 NA 0-4094
Timer Yes Yes Read / Write T 4, 9-255 0-255 PRE, ACC EN, TT, DN
Counter Yes Yes Read / Write C 5, 9-255 0-255 PRE, ACC
CU, CD, DN,
OV, UN
Control Yes Yes Read / Write R 6, 9-255 0-255 LEN, POS
EN, EU,
DN, EM, ER,
UL, IN, FD
Integer Yes Yes Read / Write N 7, 9-255 0-255 NA 0-15
ASCII Yes Yes Read A 3-999 0-999 NA 0-15
ASCII String Yes Yes Read ST 3-999 0-799 LEN, CHAR 0-15
Floating Point Yes
Yes
(Limited)
Read / Write F 3-999 0-999 NA NA
Need SLC 5/03 Series C w/OS 301 or SLC 5/04.
DTAM Plus /