110 Rockwell Automation Publication 7000-IN006B-EN-P - May 2013
Chapter 5 Commissioning the Drive
Table 2 - Oscilloscope Settings
Use the same settings on the oscilloscope when capturing waveforms for the two
Slave bridges. If you are using a 2-channel oscilloscope, then first capture two
waveforms and move them onto a wavestar worksheet and after that capture the
remaining waveforms and move them onto the same wavestar worksheet.
Sample Waveforms
Sample Waveforms captured on ACB test points showing incoming line voltage
phasing [Ch1: V2uv (red), Ch2: V2vw (yellow), Ch3: V2wu (blue)]
Figure 58 - Sample waveforms: incoming line voltage phasing
Oscilloscope Time Base Wave Form Test-Point Waveform
Label
Sheet Name
Chan. 1
10ms/div.
2U Line Voltage V2uv V2uv
Input phasingChan. 2 2V Line Voltage V2vw V2vw
Chan. 3 2W Line Voltage V2wu V2wu