114 Rockwell Automation Publication 7000-IN006B-EN-P - May 2013
Chapter 5 Commissioning the Drive
Load Test
After autotuning of the drive, run the motor on load and capture the following
waveforms at 50% load and at 100% load. If the system is not ready for 100% load
test, then capture the waveforms at the max load you are allowed to run the drive
at. Also, print variables at 50% and 100% load points. Before printing variables
make sure the drive Access Level is at SERVICE.
Capture line voltage & current waveforms at ACB test points “V2uv” &
“I2u.
Label the waveforms as “V2uv” and “I2u.
Capture motor voltage & current waveforms at ACB test points “Vuv” &
“Iu
Label the waveforms as “Vuv” and “Iu”.
Save the worksheet as “Line and Load Voltage and Current Waveforms at
1048 rpm, 31 A, for example.
Table 5 - Oscilloscope Settings
Sample Waveforms
Sample waveforms recorded on PWM drive running at full load (Ch1: Line
Voltage, Ch2 - Line Current, Ch3 - Motor Voltage, Ch4 - Motor Current)
Figure 63 - Sample waveform: PWM drive under full load condition
Oscilloscope Time Base Wave Form Test-Point Waveform
Label
Sheet Name
Chan. 1
10ms/div.
Line Voltage V2uv V2uv
{see above]
Chan. 2 Line Current I2u I2u
Chan. 3 Motor Voltage Vuv Vuv
Chan. 4 Motor Current Iu Iu