Publication 900-UM004D-EN-E - July 2010
Bulletin 900 Communications Procedures 900-TCx (CompoWay/F) 2-9
Response code
Normal Completion
Error Occurred
Table 2.8
Response
Code
Name Description
0000 Normal completion No errors were found.
Table 2.9
Response
Code
Error Name Cause
1001 Command too long The command is too long.
1002 Command too short The command is too short.
1101 Area type error The variable type is wrong.
1103 Start address out-of-range error The read start address is out of range.
110B Response too long The number of elements exceeds the
maximum/
1100 Parameter error The bit position not 00.
2203 Operation error EEPROM error
ATTENTION
!
Alarm function:
Even though alarms are not displayed on the controller's
display, they function normally in communications.