Publication 900-UM004D-EN-E - July 2010
Communications Data 3-13
Status Structure
Figure 3.1 Structure and Status Data:
Applies to the 900-TC8 only
00
16 15 14 13 12 11 10 9 8 76543 210
Bit position
Heater overcurrent (CT1)
Heater current hold (CT1)
A/D Converter Error
HS alarm output (CT1)
Display range exceeded
Input error
Control output (heating)
Control output (cooling)
HB (heater burnout) alarm output (CT1)
HB (heater burnout) alarm output (CT2)
Alarm output 1
Alarm output 2
Alarm output 3 n
Progr
am end output
Outputs Input error HB error
Vista de pagina 54