Publication 900-UM004D-EN-E - July 2010
Communications Data for Modbus 5-13
➋ The logic of the Modbus variable writing function (Operation command) is not influenced.
1336 331B Multi-SP Usage H’00000000 (0): OFF
H’00000001 (1): ON
Advanced
Setting
Function
Group
1338 331C HB ON/OFF H’00000000 (0): OFF
H’00000001 (1): ON
133A 331D MB Command Logic
Switching ➋
H’00000000 (0): OFF
H’00000001 (1): ON
133C 331E Input Error Output H’00000000 (0): OFF
H’00000001 (1): ON
133E 331F Input Shift Type H’00000000 (0): Temperature input 1-point shift
H’00000001 (1): Temperature input 2-point shift
Advanced
Setting
Function
Group
1340 3320 MV at Stop and Error Addition H’00000000 (0): OFF
H’00000001 (1): ON
1342 3321 ST Stable Range H’00000001…H’0000270F (0.1…999.9)
1344 3322 RT H’00000000 (0): OFF
H’00000001 (1): ON
1346 3323 HS Alarm H’00000000 (0): OFF
H’00000001 (1): ON
1348 3324 LBA Detection Time H’00000000…H’0000270F (0…9999)
134A 3325 LBA Function Group H’00000001…H’0000270F
(0.1…999.9 for TC/Pt multi-input models)
(0.01…99.99 for Analog input models)
134C 3326 LBA Band H’00000000…H’0000270F
(0.0…999.9 for TC/Pt multi-input models)
(0.00…99.99 for Analog input models)
134E 3327 Soak Time Unit H’00000000 (0): Minutes
H’00000001 (1): Hours
1350 3328 Alarm SP Selection H’00000000 (0): Set point during SP ramp
H’00000001 (1): Set point
1356 332B Manual MV Limit Enable H’00000000 (0): OFF
H’00000001 (1): ON
135A 332D PV Rate of Change Calculation
Period
H'00000001 to H'000003E7 (1 to 999)
135C 332E Automatic Cooling Coefficient
Adjustment
H’00000000 (0): OFF
H’00000001 (1): ON
135E 332F Heater Overcurrent Use H’00000000 (0): OFF
H’00000001 (1): ON
1360 3330 Heater Overcurrent Latch H’00000000 (0): OFF
H’00000001 (1): ON
1362 3331 Heater Overcurrent Hysteresis H'00000001 to H'000001F4 (0.1 to 50.0)
1364 3332 Control Output 1 ON/OFF Count
Alarm Set Value
H'00000000 to H'0000270F (0 to 9999)
1366 3333 Control Output 2 ON/OFF Count
Alarm Set Value
H'00000000 to H'0000270F (0 to 9999)
Table 5.10
Address Parameter Name Setting (Monitor) Value Function
Group
Four-byte
mode
Two-byte
mode