5-12 Communications Data for Modbus
1200 3200 PF Setting H'00000000 (0): None
H'00000001 (1): Run
H'00000002 (2): Stop
H'00000003 (3): RUN/STOP
H'00000004 (4): 100% AT execute
H'00000005 (5): 40% AT execute
H'00000006 (6): Alarm latch cancel
H'00000007 (7): Auto/manual switch
H'00000008 (8): Monitor/setting item
Advanced
Setting
Function
Group
1204 3203 Monitor Setting Item 1 H'00000000 (0): Disabled
H'00000001 (1): PV/SP/multi-SP
H'00000002 (2): PV/SP/MV
H'00000003 (3): PV/SP/soak time remain
H'00000004 (4): Proportional band (P)
H'00000005 (5): Integral time (I)
H'00000006 (6): Derivative time (D)
H'00000007 (7): Alarm value 1
H'00000008 (8): Alarm value upper limit 1
H'00000009 (9): Alarm value lower limit 1
H'0000000A (10): Alarm value 2
H'0000000B (11): Alarm value upper limit 2
H'0000000C (12): Alarm value lower limit 2
H'0000000D (13): Alarm value 3
H'0000000E (14): Alarm value upper limit 3
H'0000000F (15): Alarm value lower limit 3
Advanced
Setting
Function
Group
1206 3203 Monitor/Setting Item 2 H’00000000 to H’0000000F (0 to 15)
* Same as for Monitor/Setting Item 1.
1208 3204 Monitor/Setting Item 3 H’00000000 to H’0000000F (0 to 15)
* Same as for Monitor/Setting Item 1.
120A 3205 Monitor/Setting Item 4 H’00000000 to H’0000000F (0 to 15)
* Same as for Monitor/Setting Item 1.
120C 3206 Monitor/Setting Item 5 H’00000000 to H’0000000F (0 to 15)
* Same as for Monitor/Setting Item 1.
130A 3305 Cold Junction Compensation
Method
H’00000000 (0): OFF
H’00000001 (1): ON
1314 330A α H’00000000…H’00000064 (0.00…1.00)
131E 330F AT Calculated Gain H’00000001…H’00000064 (0.1…10.00)
1320 3310 AT Hysteresis H'00000001 to H'0000270F
(0.1 to 999.9 for TC/Pt universal input models)
(0.01 to 9.99 for Analog input models)
1322 3311 Limit Cycle MV Amplitude H'00000032 to H'000001F4 (5.0 to 50.0)
1328 3314 Heater Burnout Latch H’00000000 (0): OFF
H’00000001 (1): ON
132A 3315 Heater Burnout Hysteresis H’00000001…000001F4 (0.1…50.0)
132C 3316 HS Alarm Latch H’00000000 (0): OFF
H’00000001 (1): ON
132E 3317 HS Alarm Hysteresis H’00000001…000001F4 (0.1…50.0)
1334 331A Number of Multi-SP Uses H’00000000 (0): No multi-SP
H’00000001 (1): 2SP
H’00000002 (2): 4SP
Initial Setting
function group
Table 5.10
Address Parameter Name Setting (Monitor) Value Function
Group
Four-byte
mode
Two-byte
mode
Vista de pagina 93
1 2 ... 89 90 91 92 93 94 95 96 97 98 99 ... 102 103

Comentarios a estos manuales

Sin comentarios

BlackWing Projectors user manuals

The list of BlackWing Projectors products contains 1 user manuals for 1 models. All pdf user’s guides are available for download or viewing online.

Click on an alphabet below to scroll to the full list of models starting with that letter

Models Document Type
MK 2013
User Manual   MFE Mark III Mapping Scanner Operation and Maintenance Manual, 73 pages