
Parameter Descriptions 9-21
Enables/disables a software instantaneous (within 100 ms) current
trip.
Scales the value displayed by Process Display (d010).
Output Frequency x Process Factor = Process Display
1 = Reset Fault: Clears the active fault and resets the drive.
2 = Clear Buffer: Clears fault codes from parameters d007 through
d009.
Protects parameters against change by unauthorized personnel.
A098 SW Current Trip
Range: 0.0 to (Drive Rated Amps x 2)
Default: 0.0 (Disabled)
See also: N/A
A099 Process Factor (Display Scaling)
Range: 0.1 to 999.9
Default: 30.0
See also: d010
A100 Fault Clear
Range: 0 = Ready/Idle
1 = Reset Fault
2 = Clear Buffer (d007 - d009 [Fault x Code])
Default: 0 = Ready
See also: d007 - d009
A101 Program Lock
Range: 0 = Unlocked
1 = Locked
Default: 0 = Unlocked
See also: N/A
Comentarios a estos manuales