5-12
SMC Dialog Plus Controller Special Application Considerations
SMC Dialog Plus Controller
as a Bypass to an AC Drive
By using the controller as shown in Figure 5.9, a soft star
characteristic can be provided in the event that an AC drive is non-
operational.
Note: A controlled acceleration can be achieved with this scheme,
but speed control is not available in the bypass mode.
Figure 5.9 Typical Application Diagram of a Bypass Contactor for an AC
Drive
!
ATTENTION: Proper care must be taken to isolate th
AC drive from line and load potential when the
controller is energized.
Mechanical interlock required.
Customer supplied.
Many VF drives are rated 150% FLA. Because the SMC Dialog Plus controller can be
used for 600% FLA starting, separate branch circuit protection may be required.
Overload protection is included as a standard feature of the SMC Dialog Plus controller.
Power Input
VFD Branch
Protection
SMC Dialog Plus Controller
L1/1
L2/3
L3/5
T1/2
T2/4
T3/6
Motor
VFD
3-Phase
O.L.
➀➀