26 Rockwell Automation Publication 1609-QS002A-EN-P - May 2014
Appendix B EtherNet/IP Parameters
UPS Object (0x377)
Attribute
ID Need Access Rule NV Name Data Type Description of Attribute Semantics of value
1 Required Get
NV Output Rating STRUCT of: The magnitude of the nominal output
NV VA INT VA rating
NV Voltage INT Voltage rating
NV Frequency INT Frequency rating
2 Required Get
NV Input Rating STRUCT of: The magnitude of the nominal input
NV Voltage INT Voltage rating
NV Frequency INT Frequency rating
3 Required Get NV RatingBatteryVoltage INT
The magnitude of the nominal battery
voltage rating
4Required
Get NV LowTransferVoltage STRUCT of:
The Setup of low line input voltage that allowed
the UPS system transfers to the battery source
NV UpBound INT
The maximum voltage limited for the
LowTransferVoltage
NV LowBound INT
The minimum voltage limited for the
LowTransferVoltage
5
Get NV HighTransferVoltage
Array of
STRUCT of:
The Setup of high line input voltage that allowed
the UPS system transfers to the battery source
NV UpBound INT
The maximum voltage limited for the
HighTransferVoltage
NV LowBound INT
The minimum voltage limited for the
HighTransferVoltage
6 Required Get NV UPS Type INT Indicate the UPS type
on-line(1)
off-line(2),
line-interactive(3),
three-phase(4),
splite-phase(5)
All other values
reserved
7 Required Get/Set NV AutoReboot INT
In backup mode, the UPS may shutdown normally
by SDA command, dry-contact remote shutdown
signal or low battery shutdown. This command is
used to determine the unit should restart or not
next time when the power restores
on(1),
off(2)
All other values
reserved
8 Required Get/Set V ShutdownAction INT
If the value is greater than 0 the UPS performs
shutdown action that defined by ShutdownType
after the seconds. 0, aborted
9 Required Get/Set V RestartAction INT
UPS will restart after the indicated number
of minutes.
-1, aborted
10 Required Get/Set NV BuzzerAlarm UINT
UPS will keep silence but will alarm again when
next power event is occurred
alarm(1),
silence(2)
11 Required Get/Set NV BuzzerState INT If it is disabled then the UPS is always muted
enable(1),
disable(2)
12 Required Get/Set NV Sensitivity INT
The sensitivity of the UPS to utility line
abnormalities or noises
normal(0),
reduced(1),
low(2)
13 Required Get/Set NV LowVoltageTransferPoint INT
The input minimum line voltage allowed before
the UPS system transfers to battery backup
14 Required Get/Set NV HighVoltageTransferPoint INT
The input maximum line voltage allowed before
the UPS system transfers to battery backup
15 Required Get/Set V ShutdownOSDelay INT
The operating system shutdown delay time when
the input power fail
16 Required Get/Set NV UPSBootDelay UINT
Delay the UPS startup after power restores.
The power quality may not stable when power
restores, this feature let the UPS wait a period
of time to startup the system
17 Required Get/Set NV ExternalBatteryPack INT Indicate the number of external battery pack
18 Required Get V InputNumLines INT The number of input lines utilized in this device Limited 1