Rockwell Automation Publication 1609-QS002A-EN-P - May 2014 27
Appendix B EtherNet/IP Parameters
19
Required Get V Input Line Value STRUCT of: The current input values for up to InputNumLines
Frequency INT
Line frequency to the UPS system in
1/10 Hz
Voltage 1 INT
Line voltage of the UPS system in
1/10 V
20
Required
Get
V
OutputSource INT
The present source of output power. The
enumeration none(7) indicates that there is no
source of output power (and therefore no output
power), for example, the system has opened the
output breaker
normal(0),
battery(1),
bypass(2),
reducing(3),
boosting(4),
manualBypass(5),
other(6),
none(7)
21 Required Get V OutputFrequency INT
The present output frequency in
1/10 Hz
22 Required Get V OutputNumLines INT The number of output lines utilized in this device
23
Required Get V Output Line Status
Array of
STRUCT of:
The Output Line values for up to OutputNumLines
Voltage INT
line voltage of the UPS system in
1/10V
Current INT
line current of the UPS system in
1/10 A
Power INT line eal power of the UPS system in watts
Load INT line load expressed in percent of rated capacity
24 Required Get V BatteryCondition INT
The indication of the capacity remaining in the
UPS system's batteries when AC normal.
good(0),
weak(1),
replace(2)
25 Required Get V BatteryStatus INT
The indication of the capacity remaining in the
UPS system's batteries when AC failed. A value
of ok indicates that the remaining run-time is
greater than upsConfigLowBattTime. A value of
low indicates that the remaining battery run-time
is less than or equal to upsConfigLowBattTime.
A value of depleted indicates that the UPS will be
unable to sustain the present load when and if the
utility power is lost (including the possibility that
the utility power is currently absent and the UPS is
unable to sustain the output).
ok(0),
low(1),
depleted(2)
26 Required Get V BatteryCharge INT
floating(0),
charging(1),
resting(2),
discharging(3)
27 Required Get V BatteryEstimatedTime INT
Estimated time from backup to low battery
shutdown
28 Required Get V BatteryVoltage INT
The magnitude of the present battery voltage in
1/10 V
29 Required Get V BatteryCapacity INT
An estimate of the battery charge remaining
expressed as a percent of full charge
30 Required Get V Battery Temperature INT
The ambient temperature at or near the UPS
Battery casing
°C
31 Required Get/Set V TestType INT Perform the UPS Test procedure
abort(0),
generalTest(1),
batteryTest(2),
testFor10sec(3),
testUntilBattlow(4)
UPS Object (0x377)
Attribute
ID Need Access Rule NV Name Data Type Description of Attribute Semantics of value