34 Rockwell Automation Publication 1732E-UM003B-EN-E - March 2014
Chapter 6 Configure the Module Using RSLogix 5000 Software
Set Up the Hardware
In this example, a ControlLogix chassis contains the Logix5565 processor in slot
1 and a 1756-EN2T bridge module in slot 3. The 1732E ArmorBlock module is
mounted remotely.
To work along with this example set up your system as shown.
Note that in the example application, the Logix5565 controller and
1756-EN2T module (firmware version 2.3 or higher) are assumed to be in
the slots shown.
Verify the IP addresses for your programming terminal, 1756-EN2T
module and 1732E ArmorBlock Ethernet module.
Verify that you connected all wiring and cabling properly.
Be sure you configured your communication driver (for example,
AB_ETH-1 or AB-ETHIP-1) in RSLinx software.
Logix5565
1756-EN2T
EtherNet/IP
Logix5565
LINK2LINK1
NET
MOD
X10
X100
X1
AUX POWER
Local
Chassis
1732E
ArmorBlock
Logix5565
Controller (slot 1)
1756-EN2T
192.168.1.1 (slot 3)
Data
Switch
192.168.1.100
Programming
Terminal
0
1732E ArmorBlock
Ethernet Module
192.168.1.20
44971
32Slot 1
Embedded
Technology