
56 Rockwell Automation Publication 1732E-UM003B-EN-E - March 2014
Chapter 8 Specific Features of the 1732E-IB8M8SOER Sequence of Events Input Module
• Scenario #1 (no bounce) – The input turns ON and remains for the full
2 ms. In this case, the module considers the transition valid and sends the
data recorded at the transition to the controller.
Note the input was sampled as being on three different times: 0 ms, 1 ms
and 2 ms.
• Scenario #2 – The input turns ON but turns OFF before 2 ms (length of
the input filter setting) elapses. In this case, the module continues to scan
the input every millisecond. At some point, less than 2 ms later, the input
turns ON again and remains for 1 to 2 ms, the third ON sampled 1 ms
interval (in this case at 6 ms). In this case, the module considers the
transition valid and sends the data timestamped at the original transition
to the controller.
012345678
Input turns ON;
timestamp recorded
Time in milliseconds
Input remains ON for at least 2 ms; transition is considered
valid and the timestamp is sent to the controller
43671
012345678
Time in milliseconds
Input turns ON and remains ON for
1…2 ms.
The module sends the timestamp recorded
at the original transition point to the
controller.
Input turns OFF before 2 ms have elapsed.
43672
Input turns ON;
timestamp recorded
Comentarios a estos manuales