Publication 1734-UM004F-EN-E - December 2012
Calibrate Your Module 43
1. From the Configuration tab, set the Thermocouple Type to mV (no
linearization) for the channel(s) to be calibrated and download to the
module.
2. Open the Device Parameter tab and click Calibration Channel Select to
bring up your channel selections.
3. Select a channel (0 or 1), or select Both Channels.
4. Click Download to Device.
For input calibration, choose:
Input Channel 0,
Input Channel 1, or
Both Channels.