Configure Modules in RSLogix 5000 Software 61
1. Click Calibration to display the dialog.
2. Check the Calibrate checkbox to specify which channel to calibrate.
3. Under Calibrate Channels select One At a Time.
4. Click Start Calibration, which is active when:
the system is online, and
you selected at least one of the channels.
Note that you can press the F1 button on your keyboard or click Help
from the wizards and warning message that appear to get detailed
information about the procedures for calibration.
A Danger dialog appears.
5. From the Danger dialog, for a module not currently used for control,
click Continue.
The Low Value dialog appears.