46 Calibrate Your Module
2. Click Calibration Command and select Begin CJC Calibration.
3. Click the Download to Device button.
4. Using a 1734-RTB removable terminal block, apply 1000 Ω to the
selected CJC channel, referring to the wiring diagram in this section.
5. Select Accept Low CJC and download to the device.
6. Using a 1734-RTB removable terminal block, apply 3000 Ω to the
selected CJC channel.
Click calibration
command and select
Begin CJC calibration.
Then download to the
module.
Vista de pagina 55