69 Publication 1734-UM004F-EN-E - December 2012
Appendix
B
Calculate Absolute Accuracy and
Accuracy Drift
Overview
The Absolute Accuracy and Accuracy Drift with temperature specification
applies only to mV input for 1734-IT2I, and to ohms input for 1734-IR2 and
1734-IR2E modules. These specifications are listed in the POINT I/O RTD
and Isolated Thermocouple Input Module Installation Instructions,
publication 1734-IN011
.
Use mV input (1734-IT2I) or ohms input (1734-IR2 and 1734-IR2E) to verify
the Absolute Accuracy or Accuracy Drift of the POINT I/O modules.
Calculate with Formulas
Here are the formulas for calculating Absolute Accuracy and Accuracy Drift in
mV or ohms.
Absolute Accuracy Formula
Absolute Accuracy measurement is to be done at 25 C. The formula to
calculate Absolute Accuracy is as follows:
[(measured value - expected value)/ full scale] x 100 %
Accuracy Drift Formula
Accuracy Drift measurement is to be done at 2 ambient Temperature points:
T1 and T2. The formula to calculate Accuracy Drift is as follows:
[(measured value (T2) - (measured value (T1)]/ [(T2 - T1) x full scale] x
1000 000