Publication 1734-UM004F-EN-E - December 2012
Configure Modules in RSLogix 5000 Software 67
4. For Calibrate Channels, select One At a Time or In Groups to calibrate
multiple channels.
5. Click Start Calibration, which is active when:
the system is online.
you selected at least one of the channels.
Note that you can press the F1 button on your keyboard or click Help
from the wizards and warning messages that appear to get detailed
information about the procedures for calibration.
If a Danger dialog appears, the module is not inhibited.
(Calibration for channel 0 shown)
6. From the Danger dialog, for a module not currently used for control,
click Cancel and inhibit the module before you begin calibration.
The Low Value dialog appears.
7. From the Low Value dialog, click Next to start calibration.
The High Value dialog appears.