53 Publication 1734-UM004F-EN-E - December 2012
Chapter
5
Troubleshoot the Module
Overview
Read this chapter to interpret your I/O module status indicators.
Interpret the Status
Indicators
Each module has the following status indicators:
•Module
•Network
•Input 0
•Input 1
Status Indicators on the Module
Indicator Sta
stus for Module
Status Description
Module status Off No power applied to device.
Green Device operating normally.
Flashing green Device needs commissioning due to missing,
incomplete, or incorrect configuration.
Flashing red Recoverable fault is present.
Red Unrecoverable fault may require device
replacement.
Flashing
red/green
Device is in self-test.
Thermocouple
Input
Module
Status
Network
Status
1734
IT2I
NODE:
0
1
RTD
Input
Module
Status
Network
Status
1734
IR2
NODE:
0
1
Module status
Network status
Status of input 0
Status of input 1
46000
46009