3-4 Installation and Wiring
Next, plot each of the currents on the chart. If the point of intersection
falls within the operating region, your combination is valid. If not,
your combination cannot be used in a 2-slot, fixed I/O chassis. See
the example on page 3-5.
Module Current Draw – Power Supply Loading
x
OA16 and IA16 (0, 455)
OW16 and IA16 (180, 255)
Plotted from example
shown on page 3-5.
Current (mA) at 5V dc
Current (mA) at 24V dc
I/O Module 5V (mA) 24V (mA) I/O Module 5V (mA) 24V (mA) I/O Module 5V (mA) 24V (mA)
BAS 150 40 IN16 85 0 NT4 60 40
BASn 150 125 INT4 110 0 OA8 185 0
BLM10000 IO43025OA163700
BTM 110 85 IO8 60 45 OAP12 370 0
DCM 360 0 IO12 90 70 OB6EI 46 0
FIO4I 55 150 IO12DC 80 60 OB8 135 0
FIO4V55120ITB16850 OB162800
HS 300 0 ITV16 85 0 OB16E 135 0
HSTP1 200 0 IV8 50 0 OB32, series D 190 0
IA4 35 0 IV16 85 0 OB32E 190 0
IA8 50 0 IV32, series D 50 0 OBP8 135 0
IA16 85 0 KE 150 40 OBP16 250 0
IB8 50 0 KEn 150 125 OG16 180 0
IB16 85 0 NI4 25 85 OV8 135 0
IB32, series D 50 0 NI8 200 100 OV16 270 0
IC16 85 0 NI16 125 75 OV32, series D 190 0
IG16 140 0 NIO4I 55 145 OVP16 250 0
IH16 85 0 NIO4V 55 115 OW16 170 180
IM4 35 0 NO4I 55 195 OW4 45 45
IM8 50 0 NO4V 55 145 OW8 85 90
IM16 85 0 NR4 50 50 OX8 85 90