5-8 Channel Configuration, Data, and Status
Input Image - Channel Data
Word
The module input image uses 8 data word values in Class 1 and 16
data word values in Class 3. The converted voltage or current input
data values reside in I:e.0 through I:e.7 (Class 1) or I:e.0 through I:e.15
(Class 3) of the module’s input image file. When an input channel is
disabled, its data word is reset to zero.
Class 1 Data Word
Bit 1 set to
(1)
Bit 0 set to
(1)
I:e.0 channel 0 data word 14-bit integer 0 0
I:e.1 channel 1 data word 14-bit integer 0 0
I:e.2 channel 2 data word 14-bit integer 0 0
I:e.3 channel 3 data word 14-bit integer 0 0
I:e.4 channel 4 data word 14-bit integer 0 0
I:e.5 channel 5 data word 14-bit integer 0 0
I:e.6 channel 6 data word 14-bit integer 0 0
I:e.7 channel 7 data word 14-bit integer 0 0
I:e.0 channel 8 data word 14-bit integer 0 1
I:e.1 channel 9 data word 14-bit integer 0 1
I:e.2 channel 10 data word 14-bit integer 0 1
I:e.3 channel 11 data word 14-bit integer 0 1
I:e.4 channel 12 data word 14-bit integer 0 1
I:e.5 channel 13 data word 14-bit integer 0 1
I:e.6 channel 14 data word 14-bit integer 0 1
I:e.7 channel 15 data word 14-bit integer 0 1
(1) In Class 1, bit 1 determines whether data or status resides in the input image. Bit 0 determines whether
channels 0 through 7 or 8 through 15 are shown.