Publication 1746-UM001A-US-P
Channel Configuration, Data, and Status 5-9
The channel data word contains a 16-bit integer that represents the
value of the analog input channel. The tables below show the channel
data word values for various input types and data formats. The second
table shows the default full-scale values for the proportional counts
data format. The table does not imply the entire data value range is
usable resolution.
Class 3 Data Word
I:e.0 channel 0 data word 16-bit integer
I:e.1 channel 1 data word 16-bit integer
I:e.2 channel 2 data word 16-bit integer
I:e.3 channel 3 data word 16-bit integer
I:e.4 channel 4 data word 16-bit integer
I:e.5 channel 5 data word 16-bit integer
I:e.6 channel 6 data word 16-bit integer
I:e.7 channel 7 data word 16-bit integer
I:e.8 channel 8 data word 16-bit integer
I:e.9 channel 9 data word 16-bit integer
I:e.10 channel 10 data word 16-bit integer
I:e.11 channel 11 data word 16-bit integer
I:e.12 channel 12 data word 16-bit integer
I:e.13 channel 13 data word 16-bit integer
I:e.14 channel 14 data word 16-bit integer
I:e.15 channel 15 data word 16-bit integer
Channel Data Word Values for Engineering Units
Input Type Signal Range Engineering Units Engineering Units
Scale
±10V dc -10.25V to +10.25V -10250 to +10250 1 mV/step
0 to 5V dc -0.25V to +5.25V -250 to +5250 1 mV/step
1 to 5V dc +0.75V to +5.25V +750 to +5250 1 mV/step
0 to 10V dc -0.5V to +10.25V -500 to +10250 1 mV/step
0 to 20 mA -1.0 mA to 21 mA -1000 to +21000 1.0 µA/step
4 to 20 mA 3.0 mA to 21mA 3000 to 21000 1.0 µA/step
±20 mA -21 mA to 21 mA -21000 to +21000 1.0 µA/step
0 to 1 mA -0.05 mA to 1.05 mA -50 to +1050 1.0 µA/step
Comentarios a estos manuales