132 Publication IASIMP-QS010B-EN-P - October 2009
Chapter 7 Optional - Configuration of the DeviceNet Network
Create a DeviceNet Scanlist
Required with the use of any DeviceNet device
This procedure is required if you use any devices on the DeviceNet network - you must create
a scanlist that includes all of the DeviceNet devices in your network.
The examples in this section use a 1734-ADNX adapter that is has already been configured.
1. Select Network > Upload
from Network.
2. Right-click the 1734-ADNX adapter
and select Properties.
3. Click the Parameters tab
and note the parameters
shown.
You verify these
parameters at step 10
.
4. Click OK.