Publication IASIMP-QS010B-EN-P - October 2009 195
Embedded I/O Chapter 3
DC Input Filtering
The embedded IQ16F inputs can be configured to use digital filtering by input
group. Filter times can be specified for both the OFF to ON and ON to OFF
transitions.
Group 0 is used to configure inputs 0…7, and group 1 is used to configure
inputs 8…15.
Default input-filtering values are 2.0 ms. You can specify 2.0 ms, 1.0 ms, 0.5
ms, 0.1 ms, and 0.0 ms for any transition as required by your program
application.
Configure the DC Inputs
Configuration of the DC inputs is typically completed by using RSLogix 5000
software during the initial system configuration.
To configure input filter settings in RSLogix 5000 programming software,
complete these steps.
1. In the I/O Configuration tree, right-click slot 1, Embedded IF16Q
Discrete Inputs and choose Properties.
IMPORTANT
DC input configuration can be carried-out only when the
packaged controller is in Program or Remote Run modes.